首页 | 本学科首页   官方微博 | 高级检索  
     

基于软件优化的D-STATCOM新型控制策略
引用本文:常鲜戎,王辉云,郭一杰,杨永华.基于软件优化的D-STATCOM新型控制策略[J].电力系统保护与控制,2014,42(4):117-121.
作者姓名:常鲜戎  王辉云  郭一杰  杨永华
作者单位:新能源电力系统国家重点实验室,华北电力大学,河北 保定 071003;新能源电力系统国家重点实验室,华北电力大学,河北 保定 071003;新疆电力公司乌鲁木齐电业局,新疆 乌鲁木齐 830011;佛山市发电厂,广东 佛山 528000
摘    要:控制延时会导致配电网静止同步补偿器(D-STATCOM)对谐波抑制和无功补偿的精度降低。为改善传统控制策略滞后时间长、补偿效果差的缺点,提出了一种基于软件优化的新型控制策略。通过对D-STATCOM补偿指令电流的特性进行分析,对软件流程进行相应调整,缩短了谐波和无功补偿指令电流的计算延时,使补偿滞后大大减少,谐波抑制和无功补偿的精度得到明显提高。该策略无需复杂算法,实现简单、有效。在Matlab/Simulink环境中进行了仿真分析,并且研制了一台容量为10 kVA的三相四线制D-STATCOM实验样机进行验证,结果证明了新型控制策略的正确性和可行性。

关 键 词:配电网静止同步补偿器  软件优化  补偿滞后  谐波抑制  无功补偿
收稿时间:6/3/2013 12:00:00 AM
修稿时间:9/5/2013 12:00:00 AM

A novel control strategy based on software optimization for D-STATCOM
CHANG Xian-rong,WANG Hui-yun,GUO Yi-jie and YANG Yong-hua.A novel control strategy based on software optimization for D-STATCOM[J].Power System Protection and Control,2014,42(4):117-121.
Authors:CHANG Xian-rong  WANG Hui-yun  GUO Yi-jie and YANG Yong-hua
Affiliation:State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Baoding 071003, China;State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Baoding 071003, China;Urumqi Electric Power Bureau, Xinjiang Electric Power Corporation, Urumqi 830011, China;Foshan Thermal Power Plant, Foshan 528000, China
Abstract:Control delay significantly affects the performance of distribution static synchronous compensator (D-STATCOM) in harmonic suppression and reactive power compensation. To overcome the drawback of the conventional control method, which has long compensation delay and low compensation accuracy, a novel control strategy based on software optimization is proposed. Software flow is adjusted based on the analysis of the reference compensation currents. It shortens the calculation delay of harmonics and reactive power compensation reference current, so compensation delay occurs less and compensation accuracy of harmonic suppression and reactive power compensation is improved. Results obtained by D-STATCOM simulations system built in Matlab/Simulink and prototype experiment of a 10 kVA three-phase four-wire D-STATCOM show the validity and feasibility of the proposed strategy.
Keywords:D-STATCOM  software optimization  compensation delay  harmonic suppression  reactive power compensation
本文献已被 CNKI 等数据库收录!
点击此处可从《电力系统保护与控制》浏览原始摘要信息
点击此处可从《电力系统保护与控制》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号