首页 | 本学科首页   官方微博 | 高级检索  
     

某电厂电压互感器铁磁谐振案例的分析及对策
作者姓名:王权  李炜
作者单位:葛洲坝水力发电厂,湖北省宜昌市443002
摘    要:文章介绍了一起某电厂主变压器倒挂运行时,电压互感器发生分频谐振,导致主变压器低压侧开口三角电压报警动作的案例.结合现场检查处理情况,对铁磁谐振的原理进行了分析,并根据现场实际情况提出了变更运行方式、装设消谐电阻及消谐装置等应对措施.

关 键 词:主变压器倒挂  分频谐振  过电压

Analysis and Countermeasures of Voltage Transformer Ferromagnetic Resonance Case in a Hydropower Plant
Authors:WANG Quan  LI Wei
Affiliation:(Gezhouba Hydropower Plant,Yichang,443002,China)
Abstract:This paper introduces a case of voltage transformer frequency division resonance occurring when the main transformer is running upside down in a hydropower plant,which leads to the voltage alarm of the open-delta connection in main transformer lowvoltage side.The principle of ferromagnetic resonance is analyzed in combination with the on-site inspection and treatment,some countermeasures are put forward according to the actual situation,such as changing the operation mode,installing the harmonic elimination resistor and the harmonic elimination device.
Keywords:main transformer inverted operation  frequency division resonance  overvoltage