首页 | 本学科首页   官方微博 | 高级检索  
     


Simulation studies on gax based Kalina cycle for both power and cooling applications
Authors:C.P. Jawahar  R. Saravanan  Joan Carles Bruno  Alberto Coronas
Affiliation:1. Department of Mechanical Engineering, Karunya University, Coimbatore 641 114, India;2. Department of Mechanical Engineering, Anna University, Chennai 600 025, India;3. Universitat Rovira I Virgili, Group of Applied Thermal Engineering, Tarragona 43007, Spain
Abstract:A detailed parametric analysis is carried out on both simple and GAX based combined power and cooling cycle. The effect of various parameters such as heat source temperature, refrigeration temperature, sink temperature, split ratio (refrigerant flow ratio between power and cooling systems), split factor (solution flow ratio between absorber and GAX heat exchanger) on the performance of the cycle is studied. The results of the analysis show that using the GAX heat exchanger about 20% of internal heat is recovered within the cycle. The optimum split factor is 0.8–0.9 and the split ratio is 0.5:0.5. The maximum combined thermal efficiency of 35–45% and coefficient of performance of about 0.35 is attained at the optimum conditions.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏