摘 要: | This paper calculates and researches on lightning accident of ±500 kV Xing-An DC transmission line in Guangdong based on ATP-EMTP and the simulation calculation model of the HVDC has been constructed. The results show that: when a lightning current strikes to the positive polar conductor of double circuit transmission line and the flashover of insulator strings occurs, as the over-voltage wave propagating along the lines due to the coupling effect between the conductors, the grounding electrode lines would produce the coupling voltage wave, which makes the flashover of the insulator strings occur at the different place along the grounding electrode lines, the unbalanced current of the grounding polar line is produced due to the insulator strings flashover and the unbalanced current exists for a long time, when the unbalanced current is up to the locking condition, the negative polar conductor is locked and the double-pole block fault occurs. In the paper, some effective measures are given to prevent this accident.
|