首页 | 本学科首页   官方微博 | 高级检索  
     


Determination of the amount of thermal energy in the tanks of buildings heating systems
Affiliation:1. Laboratory of Technology and Policy of Energy and Environment, School of Science and Technology, Hellenic Open University, Parodos Aristotelous 18, 26335 Patras, Greece;2. Department of Chemical Engineering, School of Engineering, Nazarbayev University, Astana, Kazakhstan;3. School of Production Engineering and Management, Technical University of Crete, Chania, Greece
Abstract:The distribution of temperature according to the height in the heat storage stratified water tanks designed for the heating of premises is uneven. In order to determine possible thermal energy amount stored in the tank it is necessary to know the residual water temperature in the tank. In the experiments with vertical thermal energy storage tanks of 0.31, 0.9 and 1.5 m diameter, we determined that at a duration of charging of 8 h, and discharging of 16 h, the value of temperature transitional zone height at 90% probability is 0.47±0.03 m. Using analytical methods we worked out carry-overs for the determination of residual temperature of heat accumulating tanks with external and internal heat sources. It was determined that in the heat storage tanks with internal heat source fitted at the bottom of the tank the residual water temperature is higher, and the amount of accumulated thermal energy is lower than in the tanks with external heat source.
Keywords:
本文献已被 ScienceDirect 等数据库收录!