三相并网逆变器比例复数积分电流控制技术
引用本文:郭小强,邬伟扬,赵清林,王立乔. 三相并网逆变器比例复数积分电流控制技术[J]. 中国电机工程学报, 2009, 29(15): 8-14
作者姓名:郭小强  邬伟扬  赵清林  王立乔
作者单位:电力电子节能与传动控制河北省重点实验室(燕山大学电气工程学院)
基金项目:国家自然科学基金重点项目(50837003);河北省自然科学基金项目(E2008000801)。
摘    要:传统PI控制无法消除并网交流电流稳态误差,但关于稳态误差存在的根本原因相关文献描述较少。为揭示其本质,首先建立并网电流控制模型,然后通过叠加定理和频域分析得出结论:并网交流电流零稳态误差控制条件为:系统控制器在并网电流频率处具有无穷大增益,而PI控制不具有该特性。在该结论基础上,提出一种可消除并网交流电流稳态误差的比例复数积分(proportional complex integral, PCI)控制,给出一套控制器参数整定方法,并采用TMS320F2812 DSP实现系统的数字化控制。在理论分析的基础上进行仿真和实验研究,通过与PI控制对比验证PCI控制的有效性。

关 键 词:三相并网逆变器  电流控制  稳态误差分析  比例复数积分控制
收稿时间:2008-07-11
修稿时间:2008-10-14

Current Regulation for Three-phase Grid-connected InvertersBased on Proportional Complex Integral Control
GUO Xiao-qiang,WU Wei-yang,ZHAO Qing-lin,WANG Li-qiao. Current Regulation for Three-phase Grid-connected InvertersBased on Proportional Complex Integral Control[J]. Proceedings of the CSEE, 2009, 29(15): 8-14
Authors:GUO Xiao-qiang  WU Wei-yang  ZHAO Qing-lin  WANG Li-qiao
Affiliation:Key Lab of Power Electronics for Energy Conservation and Motor Drive of Hebei Province (College of Electrical Engineering, Yanshan University)
Abstract:Proportional plus integral (PI) control is conventionally regarded as an unsatisfactory solution for ac grid-connected inverter systems because it cannot eliminate steady-state amplitude and phase errors. Unfortunately, few literatures discuss the nature of this problem. In order to clarify the point, the linear model for the grid current control is built, based on which a crucial conclusion is reached in virtue of the superposition theorem and frequency-domain analysis: Zero steady-state error control for grid-connected inverters is obtained on condition that the controller has the infinite gain at the excited frequency, which is not the case for PI control. Based on this conclusion, a novel proportional complex integral (PCI) control is proposed, which extends the conventional real domain control into the unconventional complex domain in a mathematic way. A step-by step parameter design procedure for PCI control is given. The control system is digitally implemented with TMS320F2812 DSP. Simulation and experiments are carried out based on the theoretical analysis, and the effectiveness of the proposed PCI control is verified by an apple to apple comparison with PI control.
Keywords:three-phase grid-connected inverters  current control  steady-state error analysis  proportional complex integral control