从一起事故谈高压交联聚乙烯电缆的检测 |
| |
引用本文: | 石开翔.从一起事故谈高压交联聚乙烯电缆的检测[J].装备制造技术,2009(1). |
| |
作者姓名: | 石开翔 |
| |
作者单位: | 桂林供电局,广西,桂林,541002 |
| |
摘 要: | 某变电站110kv电缆终端头在运行不久,即发生终端头绝缘击穿事故.通过这起事故,分析对比了几种常用的电缆检测方法.提出GIS的进线电缆头在投入运行后,应进行一次在线局部放电检测,如果有务件可进行定期检测,使之更能保证高压电缆的安全运行.
|
关 键 词: | 电缆头 交流耐压试验 在线局部放电检测 |
Discussion on High Voltage Cross Linked Polyethylene Detection Method by an Accident |
| |
Authors: | SHI Kai-xiang |
| |
Affiliation: | Guilin Power Grid;Guilin Guangxi 541002;China |
| |
Abstract: | A 110kV substation cable terminations insulation breakdown occurred so after it been putted into operation.By the accident,The author analysis and comparise several commonly used methods of detection cable.The author think the GIS high voltage cable terminations should been an on-line partial discharge detect soon after it put into operation,if the conditions to carry out testing on a regular basis,it will better to ensure the safe operation of high voltage cable. |
| |
Keywords: | tag AC voltage withstand test On-line partial discharge detecting technology |
本文献已被 CNKI 维普 万方数据 等数据库收录! |
|