首页 | 本学科首页   官方微博 | 高级检索  
     


Airflow Management in a Contained Cold Aisle Using Active Fan Tiles for Energy Efficient Data-Center Operation
Authors:Vaibhav K. Arghode  Vikneshan Sundaralingam  Yogendra Joshi
Affiliation:1. George W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta, Georgia, USAvarghode@iitk.ac.in;3. George W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta, Georgia, USA
Abstract:Generally, passive perforated tiles are used in a data center and the supplied airflow rate is underprovisioned; thus, the balance of the server air requirement is met by the hot air in the room, resulting in higher server inlet temperatures. Full provisioning of the supplied airflow rate and containing the cold aisle is expected to minimize the hot air leakage in the cold aisle, resulting in uniform and lower server inlet temperatures. Thus, the supply air temperature can be raised, resulting in energy savings at the chiller plant. Supplying extra air can be achieved using active perforated tiles, having multiple fans installed on them. In this paper, the underprovisioned case using passive tiles and the fully provisioned case using active tiles are investigated for both open and contained aisle conditions. Thermal field measurements suggest lower and uniform server inlet temperatures for the case with contained aisle as compared to open aisle and for the fully provisioned case using active tiles as compared to the underprovisioned case using passive tiles. System-level energy calculations suggests that containing the cold aisle results in lower (improved) power usage effectiveness (PUE); however, use of active tiles does not seem to improve the PUE.
Keywords:
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号