首页 | 本学科首页   官方微博 | 高级检索  
     


The COP of absorption and resorption heat pumps with ammonia-water as working fluidLe coefficient de performance des pompes de chaleur à absorption et à résorption avec de l'eau-ammoniac comme fluide de travail
Authors:HD Baehr
Affiliation:The author is from the Institut für Thermodynamik, Hochschule der Bundeswehr Hamburg, Hamburg, Federal Republic of Germany
Abstract:A study has been made of the use of an absorption heat pump for the heating of buildings. With the aid of a computerized parameter study, one can evaluate the COP that can be achieved with single-stage absorption heat pumps as a function of external parameters and the irreversibilities in the components of the heat pump. An NH3H2O mixture was used. The condenser was replaced by a resorber in order to avoid the excessive pressure in the former. The COP is thus evaluated for this resorption cycle as a function of the resorption pressure. The absorber pressure and the temperature of the weak solution leaving the generator were optimized in order to achieve a better COP.