首页 | 本学科首页   官方微博 | 高级检索  
     

基于多源感知的开关柜绝缘缺陷检测技术
引用本文:曹培,徐鹏,贺建明,高凯,田昊洋,季怡萍. 基于多源感知的开关柜绝缘缺陷检测技术[J]. 中国电力, 2021, 54(10): 117-124,133. DOI: 10.11930/j.issn.1004-9649.202009053
作者姓名:曹培  徐鹏  贺建明  高凯  田昊洋  季怡萍
作者单位:1. 国网上海市电力公司电力科学研究院,上海 200437;2. 同济大学 电子与信息工程学院,上海 201804
基金项目:国家自然科学基金资助项目(U1966210);中央高校基本科研业务费专项(超材料雷达智能感知技术研究,22120190222)
摘    要:绝缘故障在电气设备故障中占很大比例,在缺陷潜伏阶段将其检测并消除是防止故障发生的重要策略.绝缘缺陷通常伴随温升或局部放电现象,因此可将其作为判断设备绝缘状态的重要依据.红外光电传感器可检测设备的温度,紫外光电传感器可检测设备局放产生的紫外脉冲信号.以开关柜内电缆终端缺陷为例,构建了一个红外和紫外光电传感同步采集装置,基...

关 键 词:光电传感器  多源感知  开关柜  电缆终端  缺陷检测
收稿时间:2020-09-07
修稿时间:2021-08-27

A Intelligent Method for Insulation Defect Detection of Switchgear Based on Multi-source Sensing
CAO Pei,XU Peng,HE Jianming,GAO Kai,TIAN Haoyang,JI Yiping. A Intelligent Method for Insulation Defect Detection of Switchgear Based on Multi-source Sensing[J]. Electric Power, 2021, 54(10): 117-124,133. DOI: 10.11930/j.issn.1004-9649.202009053
Authors:CAO Pei  XU Peng  HE Jianming  GAO Kai  TIAN Haoyang  JI Yiping
Affiliation:1. State Grid Shanghai Electric Power Research Institute, Shanghai 200437, China;2. College of Electronics and Information Engineering, Tongji University, Shanghai 201804, China
Abstract:Insulation fault accounts for a large proportion in electrical equipment faults, so it is an important strategy to detect and eliminate the faults in their latent phase. Insulation defects are usually accompanied by temperature rise or partial discharge, which can be used as an important basis for judging the insulation status of the equipment. The infrared photoelectric sensor can detect the temperature of the equipment, and the ultraviolet photoelectric sensor can detect the ultraviolet pulse signal generated by partial discharge of the equipment. In this paper, taking the cable terminal defects in the switch cabinet as an example, an infrared and ultraviolet photoelectric sensor synchronous acquisition device is constructed. Based on the adaptive fuzzy neural network, an intelligent detection method is proposed with combining two information sources of temperature rise and partial discharge. The experimental results show that compared to the information detection with single sensor, the diagnosis algorithm based on multi-source sensing significantly improves the accuracy of equipment defect diagnosis. The proposed method can provide a new research idea for identification and diagnosis of insulation defects of switchgear.
Keywords:photoelectric sensor  multi-source sensing  switchgear  cable terminal  defect detection  
点击此处可从《中国电力》浏览原始摘要信息
点击此处可从《中国电力》下载全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏