大容量SVC相控电抗器对站用低压直流电源的影响分析及防范措施
引用本文:温才权,全杰雄,周凯,潘龙斌,李成. 大容量SVC相控电抗器对站用低压直流电源的影响分析及防范措施[J]. 中国电力, 2021, 54(12): 45-53. DOI: 10.11930/j.issn.1004-9649.202102078
作者姓名:温才权  全杰雄  周凯  潘龙斌  李成
作者单位:1. 南方电网超高压输电公司梧州局, 广西 梧州 543002;2. 四川大学 电气信息学院, 四川 成都 610065
基金项目:南方电网有限公司科技项目(提高二次系统抗干扰性能关键技术研究,CGYKJXM20180555;提高SVC系统运行可靠性关键技术研究,GY2014-2-0009)。
摘    要:大容量静态无功补偿装置(static var compensator,SVC)相控电抗器对站用低压直流电源影响问题特殊且严重。为深入了解SVC对厂站低压直流电源的影响,对某变电站SVC现场设备进行实测,进而对SVC及附近区域建立三维电磁场仿真模型。通过与现场的实测值进行对比,并在实验室建立等比例模型验证仿真的等效性,在此基础上分析在电抗器敷设不同的屏蔽材料对直流电源电能质量改善情况以及带来的衍生问题。结果表明:大型SVC相控电抗器对厂站低压直流电源的影响已超过规程允许值,而敷设硅钢片、铝板、铁板均可有效降低干扰,并且带来的电感变化、发热等情况在可接受范围内。

关 键 词:静态无功补偿装置  直流电源  电能质量  保护误动系数  对地电压偏移系数  
收稿时间:2021-02-23
修稿时间:2021-09-24

Analysis on Influence of Large Capacity SVC Reactor on Low Voltage DC Power Supply for Station and Preventive Measures
WEN Caiquan,QUAN Jiexiong,ZHOU Kai,PAN Longbin,LI Cheng. Analysis on Influence of Large Capacity SVC Reactor on Low Voltage DC Power Supply for Station and Preventive Measures[J]. Electric Power, 2021, 54(12): 45-53. DOI: 10.11930/j.issn.1004-9649.202102078
Authors:WEN Caiquan  QUAN Jiexiong  ZHOU Kai  PAN Longbin  LI Cheng
Affiliation:1. CSG EHV Power Transmission Company Wuzhou Office, Wuzhou 543002, China;2. School of Electrical Engineering and Information, Sichuan University, Chengdu 610065, China
Abstract:The influence of phase controlled reactors of a large capacity SVC on the low voltage DC power supply of a power substation can be very serious. In order to understand this influence, field measurement of SVC is carried out in a substation. Furthermore, a three-dimension electromagnetic field simulation model is established for SVC and its adjacent area. A full-scale model is established in the laboratory to verify the equivalence of the simulation results through comparison with the field measurement. An analysis is made on the improvement of DC power quality brought about by different shielding materials and related problems. The results show that the influence of phase controlled reactors of a large capacity SVC on the low voltage DC power supply of a power substation has exceeded the allowable value stipulated by relevant code, and the layout optimization of silicon steel sheet, aluminum plate and iron plate can effectively reduce the interference, and the resulting inductance change and heating are acceptable.
Keywords:static var compensator  DC power supply  power quality  risk coefficient for protection malfunction  voltages to ground offset coefficient  