Abstract: | A new high-speed protection technique based on fault generated high frequency (HF) voltage signals is developed and applied to the protection of EHV series compensated power transmission lines. It is a nonunit protection technique as it relies totally on locally derived information, but it has the discriminative properties normally associated with unit protection schemes. The protection scheme has been designed using CAD techniques including emulation of analogue interfaces and hardware. It is shown that the new relay scheme is able to overcome many difficult protection problems encountered on such EHV power lines using conventional methods, and discriminates clearly between internal and external faults, producing a fast trip output |
| |