首页 | 本学科首页   官方微博 | 高级检索  
     

带约束条件的CO_2热泵热水系统高压控制方程
引用本文:王磊,梁星宇,邵亮亮,张春路. 带约束条件的CO_2热泵热水系统高压控制方程[J]. 制冷学报, 2018, 39(1): 20-27
作者姓名:王磊  梁星宇  邵亮亮  张春路
作者单位:同济大学机械与能源工程学院 制冷与低温工程研究所,同济大学机械与能源工程学院 制冷与低温工程研究所,同济大学机械与能源工程学院 制冷与低温工程研究所,同济大学机械与能源工程学院 制冷与低温工程研究所
摘    要:系统高压的优化与控制在提升跨临界CO_2系统效率方面至关重要。在CO_2热泵热水系统中,传统的高压控制方程中仅考虑了气体冷却器侧的出口温度而忽略实际应用中对出水温度的要求和温度夹点,导致系统性能大大降低。本文针对温度夹点和进出水温等约束的影响,建立了有约束的气冷器模型,并对系统高压进行了优化。采用实验设计以及统计学方法确定影响最优高压的主要因素,通过最小二乘法回归出最优高压控制方程。使用该高压控制方程的系统平均COP损失1.8%,最大COP损失8.7%,可以更好地满足实际应用。

关 键 词:CO2热泵热水;高压控制;约束模型;实验设计
收稿时间:2017-03-12

A Constrained High-pressure Control Equation for CO2 Heat Pump Water Heating System
Wang Lei,Liang Xingyu,Shao Liangliang and Zhang Chunlu. A Constrained High-pressure Control Equation for CO2 Heat Pump Water Heating System[J]. Journal of Refrigeration, 2018, 39(1): 20-27
Authors:Wang Lei  Liang Xingyu  Shao Liangliang  Zhang Chunlu
Affiliation:Institute of Refrigeration and Cryogenics, School of Mechanical Engineering, Tongji University,Institute of Refrigeration and Cryogenics, School of Mechanical Engineering, Tongji University,Institute of Refrigeration and Cryogenics, School of Mechanical Engineering, Tongji University and Institute of Refrigeration and Cryogenics, School of Mechanical Engineering, Tongji University
Abstract:The optimization and control of discharge pressure is important in transcritical CO2 heat pump water heating systems. The traditional high-pressure control equation simply takes the exit temperature of the gas cooler into account, neglecting the impacts of the pinch point and the outlet temperature of water, which might lead to a huge coefficient of performance (COP) loss in applications. In this paper, we report the development of a constrained gas cooler model by considering the influence of the pinch point and water inlet and outlet temperatures. The main impact factors of the optimum high pressure are determined through the design of experiments and statistical methods. Consequently, a new constrained optimal high-pressure control equation using least-squares regression is proposed. Based on the new control equation, the system COP loss is 1.8% in average (maximum 8.7%), providing better reliability for engineering practices.
Keywords:CO2 heat pump water heater   high pressure control   constrained model   design of experiment
本文献已被 CNKI 等数据库收录!
点击此处可从《制冷学报》浏览原始摘要信息
点击此处可从《制冷学报》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号