Failure analysis: Vapor overheads discharge line for high level radioactive waste evaporator |
| |
Authors: | C F Jenkins |
| |
Affiliation: | (1) Westinghouse Savannah River Company, SRS, Bldg 730-A, 29802 Aiken, SC |
| |
Abstract: | A 2 in. schedule 40 steel (60.3 mm diameter, 3.91 mm wall) core pipe in an evaporator overheads discharge line broke at several
locations downstream from a section of the line that bridges a road. The failure occurred during pump restart. Fish mouth
openings that developed along the pipe seams were initiated at lack of fusion defects in the pipe welds. Full drainage of
the water from the pipe did not occur when the pump was shut down because such drainage created an upstream vacuum in the
piping system. Freezing of water in the pipe (the line was not heat traced) and water hammer during pump restart each contributed
to the extensive deformation and tearing observed at the breaks. The weld flaws served as crack initiation sites and the water
hammer provided the overpressure that led to the fish mouth fracture. The pipe was replaced and a vacuum break was installed
to eliminate the drainage problem. |
| |
Keywords: | overpressure pipe burst pipe seam flaws vacuum effects water hammer |
本文献已被 SpringerLink 等数据库收录! |