首页 | 本学科首页   官方微博 | 高级检索  
     


New fault-location method for a single multiterminal transmission line using synchronized phasor measurements
Authors:SM Brahma
Affiliation:Electr. Eng. Dept., Widener Univ., Chester, PA, USA;
Abstract:This paper describes a new iterative method to locate a fault on a single multiterminal transmission line. The method uses synchronized voltage and current measurements from all terminals. Using positive-sequence components of the prefault and postfault waveforms, positive-sequence source impedances are estimated. Using these source impedances and the line data, the positive-sequence bus impedance matrix (Z/sub bus/) is formed. Using the properties of Z/sub bus/, an iterative algorithm is proposed. The algorithm first identifies the faulted section and then locates the fault on this section. This algorithm is applied to the data obtained from the Electromagnetic Transients Program simulation of a multiterminal transmission line. The simulation results show that the distinctive features of this method are that it performs with very high accuracy for all types of faults at different fault locations and is practically immune to fault resistance.
Keywords:
设为首页 | 免责声明 | 关于勤云 | 加入收藏