使用风机盘管的房间的舒适性实测研究
引用本文:袁昌立. 使用风机盘管的房间的舒适性实测研究[J]. 建筑科学, 2007, 23(6): 64-67
作者姓名:袁昌立
作者单位:武汉科技学院,环境与城建学院,武汉,430073
摘    要:本文运用实测方法,对一采用风机盘管设备的办公室内的温度场、速度场进行了测量,并运用实测数据对风机盘管的舒适性进行了分析,结果表明舒适性不能满足要求。设备选择过大、送风温差过大、新风短路是造成这一现象的主要原因。在实际工程中,对风机盘管的使用应注意舒适性的要求,风机盘管的选择要恰当,同时应注意配套的新风机组。

关 键 词:风机盘管  舒适性  送风温差  测量
文章编号:1002-8528(2007)06-0064-04
收稿时间:2007-01-18
修稿时间:2007-01-18

Measurement Study on Indoor Comfortability with Fan-coil Units
YUAN Chang-li. Measurement Study on Indoor Comfortability with Fan-coil Units[J]. Building Science, 2007, 23(6): 64-67
Authors:YUAN Chang-li
Abstract:In this paper,the measurement results of temperature field and velocity field in an office equipped with fan-coil equipment were firstly presented, and then the comfort level was analyzed.It was indicated that the indoor comfort level could not be accepted.This was mainly caused by the over-sized equipment,large supply-air temperature difference,and fresh air short circuit.It had been pointed out that more attention should be paid to comfort requirement when fan-coil units were used,moreover,both fan-coil units and fresh-air units should be properly selected.
Keywords:fan-coil unit  comfortability  supply-air temperature difference  measurement