SELECTION OF SAMPLING PERIOD FOR AUTOMATIC GENERATION CONTROL |
| |
Authors: | M L KOTHARI J NANDA LAKSHMAN HARI |
| |
Affiliation: | 1. Department of Electrical Engineering , Indian Institute of Technology , Delhi Hauz Khas, New Delhi, 110016, India;2. Power Grid Corporation of India Limited , New Delhi, India |
| |
Abstract: | ABSTRACT The paper presents the analysis of automatic generation control (AGC) of a two-equal area reheat thermal system in the presence of generation rate constraints considering a discrete-continuous time mathematical model. The effect of variation of sampling period on optimum integral gain setting and system dynamic performance has been analyzed considering supplementary controllers based on conventional area control errors (ACEs) and new area control errors (ACENs). Investigations reveal that the optimum integral gain setting and system dynamic performance are hardly affected over a wide range of sampling period T for controllers based on conventional ACEs. Studies also reveal that the permissible sampling period is further enhanced with integral controllers based on new area control errors (ACENs). |
| |
Keywords: | |
|
|