钉头管自支承式换热器的耦合传热及流场数值模拟研究
引用本文:刘娇洋,江楠. 钉头管自支承式换热器的耦合传热及流场数值模拟研究[J]. 压力容器, 2010, 27(6): 28-32,42. DOI: 10.3969/j.issn.1001-4837.2010.06.006
作者姓名:刘娇洋  江楠
作者单位:华南理工大学化工机械研究所,广州,510640
摘    要:对钉头管自支承式换热器的结构进行合理简化,建立数值模型,用FLUENT软件对其温度场和流场进行数值模拟,分析比较了钉头管自支承式换热器对空气、水、润滑油3种介质的强化传热效果。结果表明钉头管自支承式换热器对粘度较小的空气介质效果更明显,其强化传热系数可达光管结构的1.7倍左右,压降为光管结构的1.04-1.08倍。

关 键 词:自支承式换热器  钉头管  强化传热  数值模拟  流场分析

Coupled Heat Transfer and Numerical Simulation for Pin-finned Tubes Self-support Heat Exchanger
Liu Jiao-yang,Jiang Nan. Coupled Heat Transfer and Numerical Simulation for Pin-finned Tubes Self-support Heat Exchanger[J]. Pressure Vessel Technology, 2010, 27(6): 28-32,42. DOI: 10.3969/j.issn.1001-4837.2010.06.006
Authors:Liu Jiao-yang  Jiang Nan
Affiliation:(Machinery and Automotive Engineering Institute, South China University of Technology, Guangzhou 510640, China)
Abstract:According to the structure of pin - finned tubes self - support heat exchanger, the structure is simplified and numerical model is built. The temperature field and flow field are simulated by FLUENT software. The heat transfer enhancement effect to air, water and lubricating oil is analyzed. It shows that the pin - finned tubes self - support heat exchanger is good at heat transfer enhancement especially to low viscosity medium such as air, the heat transfer coefficient of pin - finned tubes self - support heat ex- changer is about 1.7 times that of the plain tubes and the pressure drop is about 1.04 - 1.08 times.
Keywords:self - support heat exchanger  pin - finned tube  heat transfer enhancement  numerical simulation  flow field distribution