首页 | 本学科首页   官方微博 | 高级检索  
     


Modeling and analysis of current harmonic distortion from grid connected PV inverters under different operating conditions
Affiliation:1. School of Mechanical and Electrical Engineering, University of Electronic Science and Technology of China, Chengdu 611731, China;2. Electrical Power and Machines Engineering Department, Faculty of Engineering, Tanta University, Tanta 31511, Egypt
Abstract:Due to the fast growth of photovoltaic (PV) installations, concerns are rising about the harmonic distortion generated from PV inverters. High current total harmonic distortion (THD) occurs when PV inverters operate under light load conditions due to low solar insolation. A general model modified from the conventional control structure diagram is introduced to analyze the harmonic formation process. Causes of the current harmonics are summarized and its relationship with output power levels is analyzed. The field measurement for current harmonics is carried out at the Commonwealth Scientific and Industrial Research Organisation (CSIRO) microgrid to validate the analysis results. In particular for two-stage inverter, unlike previous papers that assume the DC-link voltage is constant, the DC-link voltage ripple is identified as the source of a series of odd harmonics. A mew periodic time-varying model is proposed by including the DC-link voltage ripple into the conventional current control loop model. This model is able to simulate the characteristics of the harmonic components and show their dependence on the DC-link voltage ripple.
Keywords:DC-link voltage ripple  Harmonics  Matlab/Simulink  Microgrid  PV inverter
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号