首页 | 本学科首页   官方微博 | 高级检索  
     


A two-stage system of nocturnal radiative and indirect evaporative cooling for conditions in Tehran
Authors:Moien Farmahini Farahani  Shahram Delfani
Affiliation:a Department of Mechanical Engineering, Tarbiat Modares University, P O Box 14115-143, Tehran, Iran
b Building and Housing Research Center (BHRC), P O Box 13145-1696, Tehran, Iran
Abstract:In this paper, the results of an investigation on a two-stage cooling system have been studied. This system consists of a nocturnal radiative unit, a cooling coil, and an indirect evaporative cooler. During the night in summer, requisite chilled water for a cooling coil unit is provided by nocturnal radiative cooling and is stored in a storage tank. During the next day, the water in the tank provides chilled water for the cooling coil unit and hot outdoor air passes through two-stages: the cooling coil unit and an indirect evaporative cooler. Three sources provide secondary air for the indirect evaporative cooler. The sources are outdoor air, the air leaving from the cooling coil, and the air leaving from the indirect stage (regenerative). The investigation has been conducted in weather conditions in the city Tehran. The results obtained demonstrate that the first stage of the system increases the effectiveness of the indirect evaporative cooler. Also, the regenerative model provides the best comfort conditions. Therefore, this environmentally friendly and energy-efficient system can be considered as an alternative to the mechanical vapor compression systems.
Keywords:Nocturnal radiative cooling  Indirect evaporative cooling  Cooling coil  Two-stage cooling systems
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏