首页 | 本学科首页   官方微博 | 高级检索  
     


The effect of air-conditioning parameters and deposition dust on microbial growth in supply air ducts
Authors:Angui Li  Xiaobin Zhu  Qingqin Wang
Affiliation:a School of Environmental and Municipal Engineering, Xi’an University of Architecture and Technology, Xi’an, Shannxi 710055, PR China
b China Academy of Building Research, Beijing 100013, PR China
Abstract:To investigate the effect of air-conditioning parameters (including temperature, relative humidity and air velocity) and deposition dust on microbial growth in supply air duct, a complete test facility according to ASHRAE Standard 62.1-2007 was constructed. A series of experiments for testing microbial concentration (including bacteria and fungus) were conducted under different working conditions (such as different temperatures and relative humidity). The air velocity was constantly kept at 2.0 m/s. Orthogonal design was employed for the analysis of test data. The results indicated that air velocity attenuation down the direction of the supply air affected dust distribution at the bottom of duct, to some extent, and the number of microorganisms was positively correlated with the quantity of dust. In the range of temperature 22-32 °C and relative humidity (RH) 40-90%, microbial growth significantly accelerated with higher temperature and RH increasing. The organic compounds composing the dust also had great impact on microbial growth. The basic researches are contributed to control the growth of microorganism and improve the indoor microenvironment in the air-conditioning room.
Keywords:Air velocity  Microorganisms  Deposition dust  Temperature  Supply air duct  Relative humidity
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号