首页 | 本学科首页   官方微博 | 高级检索  
     


In situ performance of independent humidity control air-conditioning system driven by heat pumps
Authors:Weifeng Zhu  Zhongjian Li  Shuanqiang Liu
Affiliation:a Shanghai Research Institute of Building Sciences, Shanghai 200032, China
b Department of Building Science, School of Architecture, Tsinghua University, Beijing 100084, China
Abstract:A liquid desiccant based independent humidity control (IHC) air-conditioning system driven by heat pumps is presented in this paper. The system consists of a liquid desiccant fresh air processor and a high-temperature chilled water system. The operating principles of the fresh air processor and the whole system are presented in detail. Based on the in situ system installed in an ecological building of Shanghai Research Institute of Building Sciences (SRIBS), a performance investigation was performed in summer, 2007. The measurement results show that (1) the indoor temperature and humidity both are in the specified range; (2) the supply water temperature of the high-temperature refrigerator is higher than the corresponding indoor air dew point temperature, so no condensed water would be formed on the fan-coil unit (FCU) surface; and (3) the average coefficients of performances (COPs) of the fresh air processor and the high-temperature refrigerator are 6.24 and 4.38, respectively, and the average COP of the whole IHC system is 5.28.
Keywords:IHC  Air-conditioning system  Air quality  Performance  In situ measurements  Ecological building
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号