首页 | 本学科首页   官方微博 | 高级检索  
     


Real climate experimental study of two double window systems with preheating of ventilation air
Authors:Jorge S Carlos  Helena Corvacho  JP Castro-Gomes
Affiliation:a C-MADE, Centre of Materials and Building Technologies, University of Beira Interior, Calcada Fonte do Lameiro, 6200-358 Covilhã, Portugal
b Faculty of Engineering of the University of Porto (FEUP), Civil Engineering Department, Building Division, Laboratory of Building Physics, Porto, Portugal
Abstract:This paper aims to characterize the thermal performance of a window system that consists in doubling an existing window, converting it into a ventilated double window. The air coming from the outside circulates upwards through the channel between windows and enters the building through a vent on the top of the window's case. A series of experimental measurements was conducted in a test cell exposed to real outdoor weather conditions located in a mountain region at Centre of Portugal, during heating season in order to determine how this window system can act as a heat exchanger. It was found that such window system act as an efficient heat exchanger using transmission heat losses and solar radiation to preheat ventilation air, thus reducing the building's operational energy costs. An average of about 19 m3/h of air flow rate was found with an air temperature increment within the air gap of about 6 °C, during night-time, for an indoor/outdoor temperature difference of about 16 °C. Air temperature increment reached up to 12 °C using a plastic shutter. With solar radiation, the average of that increment was about 10 °C. This is a simple and cheap building technology which can be implemented both in new and existing buildings.
Keywords:Solar heating  Ventilation air  Double window  Experimental measurements
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号