首页 | 本学科首页   官方微博 | 高级检索  
     

低压备自投装置选择性保护的探讨
引用本文:刘平,谭本刚,郑文涛.低压备自投装置选择性保护的探讨[J].低压电器,2010(9):49-50,55.
作者姓名:刘平  谭本刚  郑文涛
作者单位:三板溪水电厂,湖南,长沙,410004
摘    要:针对400 V备自投开关切换至短路母线上时往往由于备自投装置的选择性问题导致进线开关跳闸进而使得低压系统全部失电,提出了保护整定配合和区域选择性联锁的解决方案,有效避免了因低压备自投误动导致的扩大性跳闸。

关 键 词:配电系统  备用电源自投  选择性保护  区域选择性联锁

Discussion on Selective Protection of RAC in Low Voltage Distribution System
LIU Ping,TAN Bengang,ZHENG Wentao.Discussion on Selective Protection of RAC in Low Voltage Distribution System[J].Low Voltage Apparatus,2010(9):49-50,55.
Authors:LIU Ping  TAN Bengang  ZHENG Wentao
Affiliation:(Sanbanxi Hydraulic Power Plant,Changsha 410004,China)
Abstract:Aiming at that the selective protection of reserve automatic closure(RAC) in a 400 V system led to input line circuit breakers tripping to cause the power failure of the whole low voltage system when the RAC was switched to short-circuit bus,the solution of protection adjusting and zone selective interlocking(ZSI) was proposed to avoid override trip effectively by the RAC error.
Keywords:distribution system  reserve automatic closure(RAC)  selective protection  zone selective interlocking(ZSI)