首页 | 本学科首页   官方微博 | 高级检索  
     


The use of impulse ventilation for smoke control in underground car parks
Authors:João Carlos Viegas
Affiliation:Laboratório Nacional de Engenharia Civil, Av. do Brasil, 101, 1700-066 Lisboa, Portugal
Abstract:Impulse ventilation systems (IVS) are used to provide ventilation for covered car parks and to control the smoke in the event of fire. In this paper the interaction between the fire ceiling jet and the flow driven by jet fans is studied using CFD simulations. A sensitivity analysis considering important parameters as position and intensity of fire source, transversal distance between jet fans, restriction of exhaust flow rate and dimension of car park exhaust opening is carried out and rules for the design of 50 N thrust jet fans are deduced. An analytical model for the flow field near the ceiling is developed and compared with CFD simulations. This model is intended to support a first approach of the design of IVS.
Keywords:
本文献已被 ScienceDirect 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏