首页 | 本学科首页   官方微博 | 高级检索  
     


Effect of louver angle on performance of heat exchanger with serpentine fins and flat tubes in frosting: Importance of experiments in periodic frosting
Affiliation:1. Key Lab of Enhanced Heat Transfer, Ministry of Education, College of Environmental and Energy Engineering, Beijing University of Technology, Beijing 100124, China;2. Beijing Advanced Innovation Center for Future Internet Technology, Beijing University of Technology, Beijing 100124, China;1. School of Civil Engineering and Mechanics, Xiangtan University, Xiangtan City, 411105, China;2. Wenzhou Design Assembly Company Ltd, Wenzhou City, 325000, China;3. College of Civil Engineering, Hunan University, Changsha, Hunan, 410082, China
Abstract:This paper presents the air-side pressure drop and overall heat transfer coefficient characteristics for serpentine-louvered-fin, microchannel heat exchanger in periodic frosting. It focuses on quantification of the effects of louver angle on heat transfer and pressure drop and on defrost and refrost times. Nine heat exchangers differing in louver angle and fin pitch (i.e. louver angle 15° to 39° and fin pitch 12 to 18 fpi) are studied. The face velocity was 3.5 m s?1 and inlet air relative humidity of 70% and 80%.The major finding of this paper is seen in the proof that it is necessary to perform experiments in several consecutive cycles to be able to understand the situation in operation of the heat exchangers and that geometry that is the best in first frosting test does not stay the best in real operation where multiple consecutive frosting occurs.
Keywords:
本文献已被 ScienceDirect 等数据库收录!