首页 | 本学科首页   官方微博 | 高级检索  
     

一起600MW发电机氢爆事件原因分析
引用本文:梅强,解兵,王成亮.一起600MW发电机氢爆事件原因分析[J].江苏电机工程,2007,26(6):14-16.
作者姓名:梅强  解兵  王成亮
作者单位:江苏省电力试验研究院有限公司,江苏,南京,210036
摘    要:某电厂的一台600 MW氢冷发电机,在完成气体置换操作2天后进行发电机直流耐压试验,当第一相试验完成降压且绕组接地后,发电机内部发生氢爆事件.通过对发电机的结构分析及事件过程调查,导出可能的氢气来源和引爆火源,同时提出为防止类似事件的发生而应采取的措施.

关 键 词:发电机  氢气  氢爆
文章编号:1009-0665(2007)06-0014-02
修稿时间:2007年7月26日

Analysis of a 600 MW Generator's Hydrogen-explosion Event
MEI Qiang,XIE Bing,WANG Cheng-liang.Analysis of a 600 MW Generator''''s Hydrogen-explosion Event[J].Jiangsu Electrical Engineering,2007,26(6):14-16.
Authors:MEI Qiang  XIE Bing  WANG Cheng-liang
Abstract:A hydrogen-explosion event of one 600 MW hydrogen-cold generator took place in an electric power plant.Direct-current withstand voltage test was carried out after the gas-exchange operation was over for two days,when the first phase test was finished,the voltage was step down to zero and the windings were earthed,this event happened.Through the analysis to the generator structure and the investigation to the event process,the possible hydrogen source and fire source was deduced,and the measures to prevent such event from happening were given.
Keywords:generator  hydrogen  hydrogen explosion  
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏