840 MV·A主变压器磁屏蔽故障分析及处理 |
| |
引用本文: | 徐铬. 840 MV·A主变压器磁屏蔽故障分析及处理[J]. 湖北水力发电, 2016, 0(1). DOI: 10.13622/j.cnki.cn42-1800/tv.1671-3354.2016.01.014 |
| |
作者姓名: | 徐铬 |
| |
作者单位: | 长江电力技术研究中心诊断测试部,湖北宜昌,443000 |
| |
摘 要: | 某水电站1台840 MV·A主变压器在运行期间例行油色谱分析发现乙炔含量上升,影响主设备安全稳定运行。检修人员查找出故障点在上夹件磁屏蔽,并对结构进行分析,明确了故障原因是设计上的结构缺陷,提出了相应的改进设计,对该型所有主变压器的磁屏蔽进行了更换,防止了该家族性缺陷产生的安全风险。
|
关 键 词: | 水电站 主变压器 磁屏蔽 放电故障 |
Analysis and Treatment of a Magnetic Shielding Fault in 840 MVA Main Transformer |
| |
Abstract: | During the routine oil chromatographic analysis of an 840 MVA main transformer in a hydropower station, ab-normal rising of the acetylene content is observed, which could affect its safe and stable operation.Examination shows that it is caused by the magnetic shielding fault of the upper clamp.Further analysis on the structure shows that the mag-netic shielding is of certain structural defects in its design.Improvement design is then proposed correspondingly.In practice, all of the old type magnetic shielding for main transformers are replaced to prevent the safety risk due to the a-bove mentioned structural defects. |
| |
Keywords: | hydropower station main transformer magnetic shielding discharge fault |
本文献已被 CNKI 万方数据 等数据库收录! |
|