首页 | 本学科首页   官方微博 | 高级检索  
     

神农大酒店地源热泵空调系统技术方案分析
引用本文:谭超毅,王孟孟,胡海华,陈 刚,唐文斐.神农大酒店地源热泵空调系统技术方案分析[J].湖南工业大学学报,2014,28(3):1-5.
作者姓名:谭超毅  王孟孟  胡海华  陈 刚  唐文斐
作者单位:湖南工业大学 土木工程学院;湖南工业大学 土木工程学院;湖南工业大学 土木工程学院;湖南天易集团有限公司;湖南工业大学 土木工程学院
基金项目:湖南省科技重大专项基金资助项目(2011FJ1007)
摘    要:为了提高地源热泵空调系统的能效比并降低地源热泵空调系统地埋换热器的换热器面积,减小系统投资,对神农大酒店地源热泵空调系统采用不同技术方案,从系统热负荷、全年不平衡热负荷、冷却水流量、系统能效比等几方面进行理论分析,经综合比较,采用冷热一体机与热水机串联+冷却塔辅助散热的复合式系统方案优于其他方案。但此方案受制于目前市场上冷热一体机的冷凝器和热水机蒸发器的循环水流通截面积不相等,引起流动阻力增加,影响使用效果。因此开发出冷热一体机的冷凝器和热水机蒸发器的循环水流通截面积相等的产品,是科研工作者和生产厂家要解决的首要问题。

关 键 词:地源热泵空调系统  能效比  地埋换热器  换热面积  不平衡热负荷
收稿时间:2014/2/24 0:00:00

Analysis on Technology Scheme of Ground-Source Heat Pump System in Shennong Hotel
Tan Chaoyi,Wang Mengmeng,Hu Haihu,Chen Gang and Tang Wenfei.Analysis on Technology Scheme of Ground-Source Heat Pump System in Shennong Hotel[J].Journal of Hnnnan University of Technology,2014,28(3):1-5.
Authors:Tan Chaoyi  Wang Mengmeng  Hu Haihu  Chen Gang and Tang Wenfei
Affiliation:Tan Chaoyi, Wang Mengmeng, Hu Haihua, Chen Gang, Tang Wenfei (1. School of Civil Engineering, Hunan University of Technology, Zhuzhou Hunan 412007, China; 2. Hunan Tianyi Group Co., Ltd., Zhuzhou Hunan 412007, China)
Abstract:In order to improve the energy efficiency of ground-source heat pump system and reduce the system underground heat exchanger area and to lower the system investment, different technical solutions are considered in ground-source heat pump system of Shennong Hotel. After comprehensively analyzing and comparing the system heat load, the annual unbalance heat load , cooling water flow and the system energy efficiency of different solutions, the scheme of cooling and heating integrative machine with water heater series connection and cooling tower auxiliary radiation hybrid system outperforms the other schemes. However, the scheme is subject to the unequal cross-sectional area between the condenser of cooling and heating machine and the evaporator of water heater, resulting in flow resistance increases and affecting the use effect. Therefore, the key issue for researchers and manufacturers is to develop the matching condenser and evaporator with equal circulating water flow area.
Keywords:ground-source heat pump system  energy efficiency ratio  ground heat exchanger  heat exchanger area  unbalance heat load