首页 | 本学科首页   官方微博 | 高级检索  
     


Turbine generator laboratory model tests to damp torsionaloscillations with supplementary signals
Authors:Sokhey  IS Limebeer  DJN Macdonald  DC
Affiliation:Southern Electric plc, Maidenhead;
Abstract:The improvement of generator stability by the use of supplementary signals into the voltage regulator and governor loops using discrete-time linear optimal control theory has been studied with particular emphasis on providing better damping for torsional oscillations. A multi-inertia laboratory model equipped with data acquisition and control computers was constructed to model the shaft dynamics of a 660 MW Drax turbine-generator. It is shown that the shaft torsional phenomena can be adequately simulated on a micro-synchronous-generator at least as far as the dominant shaft torsional modes of vibration are concerned. The practical implementation of multi-mode linear quadratic Gaussian (LQG) controllers has been shown to enhance system stability and provide better damping to the lower frequency torsional modes, which are those most susceptible to excitation
Keywords:
设为首页 | 免责声明 | 关于勤云 | 加入收藏