500kV电容式电压互感器顶端接地对分压电容C_2的影响
引用本文:赵汝国. 500kV电容式电压互感器顶端接地对分压电容C_2的影响[J]. 电力电容器与无功补偿, 2006, 0(3)
作者姓名:赵汝国
摘    要:在新建变电站的验收中,发现电容式电压互感器(CVT)顶端接地对分压电容C2的测量值产生了影响。通过对测量C2时原理接线图的分析,知道由于顶端接地,每次测得的电容值C2均需要除以校正系数K值后,方能够得到准确的实际值,再进行前、后数据比较,可以保证每次所测得的电容值前、后具有可比性,并能够准确地判断CVT的绝缘状况是否良好。

关 键 词:电容式电压互感器(CVT)  分压电容  校正系数

The Affect of 500kV CVT's Top Terminal Grounding on the Dividing Capacitance C2
ZHAO Ru-guo. The Affect of 500kV CVT's Top Terminal Grounding on the Dividing Capacitance C2[J]. Power Capacitor $ Reactive Power Compensation, 2006, 0(3)
Authors:ZHAO Ru-guo
Abstract:In the acceptance test of new built substation,it is found that the 500kV CVT′ top terminal grounding will affect the dividing capacitance C_2.Through analysis on the connection principle of measurement,it is concluded that,due to such grounding,the reality value of C_2 must be corrected by a coefficient K.In each measurement,the measured value of C_2 should be divided by K,and the values gotten from different measurements should be compared and analyzed,thus the insulation of CVT can be determined accurately.
Keywords:Capacitor Voltage Transformer(CVT)  Dividing capacitor  Correction coefficient