变压器直流偏磁及其与接地电阻关系的研究(英文)
引用本文:蒋伟,吴广宁,肖华.变压器直流偏磁及其与接地电阻关系的研究(英文)[J].高电压技术,2008,34(12):2530-2535.
作者姓名:蒋伟  吴广宁  肖华
作者单位:School of Electrical Engineering,Southwest Jiaotong University
基金项目:Project Supported by National Natural Science Foundation of China(10476022)
摘    要:Recently years,UHVDC transmission system is paid more attention to in the field of China’s power system.It takes key part in the China electrical power development stratagem.But,many problems are caused by UHVDC system,such as DC bias,corrosion of metal underground and so on.DC bias is harm to the transformers nearby UHVDC grounding polar.In this paper,the influences of DC grounding current on transformer are introduced and some suggestions of DC bias solution were provided.And,the relationship between UHVDC Grounding Current and grounding Resistance of Substation was analyzed.Firstly,two-part network circuit was used to equivalent the grounding circuit.Then,an analysis of rules was done between DC bias current and grounding resistance.Finally,the conclusion is given that DC bias current rises fast as DC grounding resistance or AC grounding resistance rises.It drops when resistance of AC transmission line or interaction resistance between DC grounding system and AC grounding system rises.Decreasing AC grounding resistance and DC grounding resistance is important to restrain DC bias current.Increasing resistance of AC transmission line such as adding resistance into transformer neutral-point grounding is a useful way to limit DC bias current.

关 键 词:UHVDC  Mono-polar  operation  DC  bias  DC  Grounding  electrodes  grounding  resistance  excitation  current

Effects of Transformer DC Bias and the Relationship Between UHVDC Grounding Current and Grounding Resistances
Affiliation:JIANG Wei1,WU Guang-ning1,XIAO Hua1,HUANG Zhen1,2,Saleh Yahya Muhammed1,GUAN Lan1(1.School of Electrical Engineering,Southwest Jiaotong University,Chengdu 610031,China;2.Sichuan Electric Power Company,Chengdu 610061,China)
Abstract:Recently years, UHVDC transmission system is paid more attention to in the field of China's power system. It takes key part in the China electrical power development stratagem. But, many problems are caused by UHVDC system,such as DC bias, corrosion of metal underground and so on. DC bias is harm to the transformers nearby UHVDC grounding polar. In this paper, the influences of DC grounding current on transformer are introduced and some suggestions of DC bias solution were provided. And, the relationship between UHVDC Grounding Current and grounding Resistance of Substation was analyzed. Firstly, two-part network circuit was used to equivalent the grounding circuit. Then, an analysis of rules was done between DC bias current and grounding resistance. Finally, the conclusion is given that DC bias current rises fast as DC grounding resistance or AC grounding resistance rises. It drops when resistance of AC transmission line or interaction resistance between DC grounding system and AC grounding system rises. Decreasing AC grounding resistance and DC grounding resistance is important to restrain DC bias current. Increasing resistance of AC transmission line such as adding resistance into transformer neutral-point grounding is a useful way to limit DC bias current.
Keywords:UHVDC  Mono-polar operation  DC bias  DC Grounding electrodes  grounding resistance  excitation current