首页 | 本学科首页   官方微博 | 高级检索  
     


Power reduction in HPC data centers: a joint server placement and chassis consolidation approach
Authors:Ali Pahlavan  Mahmoud Momtazpour  Maziar Goudarzi
Affiliation:1. Energy Aware SYstem Laboratory (EASY Lab.), Department of Computer Engineering, Sharif University of Technology, Tehran, Iran
Abstract:Size and number of high-performance data centers are rapidly growing all around the world in recent years. The growth in the leakage power consumption of servers along with its exponential dependence on the ever increasing process variation in nanometer technologies has made it inevitable to move toward variation-aware power reduction strategies in data centers. In this paper, we address the problem of joint server placement and chassis consolidation to minimize power consumption of high-performance computing data centers under process variation. To this end, we introduce two variation-aware server placement heuristics as well as an integer linear programming (ILP)-based server placement method to find the best location of each server in the data center based on its power consumption and the data center heat recirculation model. We then incorporate a novel ILP-based variation-aware chassis consolidation technique to find the optimum task assignment solution under the obtained server placement approach to minimize total power consumption. Experimental results show that by applying the proposed joint variation-aware server placement and chassis consolidation techniques, up to 14.6 % improvement can be obtained at common data center utilization rates compared to state-of-the-art variation-unaware approaches.
Keywords:
本文献已被 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号