华东地区500 kV线路绝缘子的爬距有效利用系数
引用本文:钱之银,肖嵘,吴光亚.华东地区500 kV线路绝缘子的爬距有效利用系数[J].电网技术,2007,31(18):32-36.
作者姓名:钱之银  肖嵘  吴光亚
作者单位:1. 华东电网有限公司,上海市,黄浦区,200002
2. 华东电力试验研究院,上海市,虹口区,200437
3. 国网武汉高压研究院,湖北省,武汉市,430049
摘    要:绝缘子的积污特性和爬距有效利用系数对线路的外绝缘特性有重要的影响,这一点应在外绝缘配置时予以考虑。对华东电网常用的几种绝缘子的积污特性、爬电距离有效利用系数进行了分析和计算,同时,在污秽试验的基础上,对几种常见的绝缘子试品进行了长串耐压试验,试验结果表明,不同类型绝缘子的爬电距离有效利用系数存在较大差异。此外,对不同串型布置方式下的长串绝缘子进行人工污秽试验,试验结果表明,双悬垂I串绝缘子的单片最大污耐压小于单悬垂I串时,如果双悬垂I串绝缘子采用V型或倒V型布置,绝缘子的积污特性可得到明显改善,且其污耐压水平也将得到明显的提高。

关 键 词:500  kV线路  绝缘子  积污特性  爬距  利用系数  污闪
文章编号:1000-3673(2007)18-0032-05
修稿时间:2007-08-01

Research on Creepage Distance Utilization Coefficients of Insulators for 500 kV Transmission Lines in East China Area
QIAN Zhi-yin,XIAO Rong,WU Guang-ya.Research on Creepage Distance Utilization Coefficients of Insulators for 500 kV Transmission Lines in East China Area[J].Power System Technology,2007,31(18):32-36.
Authors:QIAN Zhi-yin  XIAO Rong  WU Guang-ya
Affiliation:1.East China Grid Co. Ltd.,Huangpu District,Shanghai 200002,China;2.East China Electric Testing &; Research Institute,Hongkou District,Shanghai 200437,China;3.SG Wuhan High Voltage Research Institute,Wuhan 430049,Hubei Province,China
Abstract:Contamination accumulation characteristics and creepage distance utilization coefficients greatly impact the external insulation characteristics, so these factors should be considered in external insulation configuration. The authors analyze and calculate the contamination accumulation characteristics and creepage distance utilization coefficients of several kinds of insulators commonly used in East China Power Grid. At the same time, on the basis of pollution test the long string withstand voltage tests for familiar insulator specimens are carried out. Test results show that there are evident differences among creepage distance utilization coefficients of different types of insulators. Besides, artificial pollution tests for long insulator strings with different arrangements are performed, and test results show that under polluted and wetted conditions the maximum withstand voltage of single chip of insulator in I-shaped double suspension insulator strings is less than that in I-shaped single suspension insulator string; if the V-shape or inverted V-shape arrangement is applied to I-shaped double suspension insulator strings, the contamination accumulation characteristics of insulators as well as its withstand voltage under pollution condition can be evidently improved.
Keywords:500 kV transmission line  insulator  contamination accumulation characteristics  creepage distance  utilization coefficients  pollution flashover