摘    要:There will be more and more AC transmission lines near oil/gas pipelines in the future.So in order to determine the safe distance between them,simple and effective methods are required for engineers to efficiently evaluate the electromagnetic effect on oil/gas pipelines due to faults of AC transmission lines.In this paper,an easily handled fitting formula is obtained based on multiple calculation results,which is the maximum voltage on the pipeline anticorrosive coating produced by 1 000 kV AC transmission line under single phase ground fault.Although the calculation results obtained from the fitting formula differ from those gained by precise calculation with softwares,the verification of the formula shows that it is applicable for engineering calculation.This research could be applied to evaluate the electromagnetic effect of 1 000 kV AC transmission line under single-phase ground fault on nearby pipelines,as well as to determine the safe distance or the maximum parallel length.

关 键 词:1  000  kV  AC  transmission  line  single-phase  ground  fault  oil/gas  pipelines  maximum  voltage  on  the  pipeline  anticorrosive  coating  fitting  formula  electromagnetic  effect  safe  distance

Engineering Calculation Method of Electromagnetic Effect on Oil/Gas Pipelines from 1000 kV AC Transmission Line Having Single-phase Ground Fault
ZHANG Wenliang,JIANG Jun,GUO Jian,LU Jiayu.Engineering Calculation Method of Electromagnetic Effect on Oil/Gas Pipelines from 1000 kV AC Transmission Line Having Single-phase Ground Fault[J].High Voltage Engineering,2012,38(9):2145-2149.
Authors:ZHANG Wenliang  JIANG Jun  GUO Jian  LU Jiayu
Affiliation:China Electric Power Research Institute
Abstract:There will be more and more AC transmission lines near oil/gas pipelines in the future.So in order to determine the safe distance between them,simple and effective methods are required for engineers to efficiently evaluate the electromagnetic effect on oil/gas pipelines due to faults of AC transmission lines.In this paper,an easily handled fitting formula is obtained based on multiple calculation results,which is the maximum voltage on the pipeline anticorrosive coating produced by 1 000 kV AC transmission line under single phase ground fault.Although the calculation results obtained from the fitting formula differ from those gained by precise calculation with softwares,the verification of the formula shows that it is applicable for engineering calculation.This research could be applied to evaluate the electromagnetic effect of 1 000 kV AC transmission line under single-phase ground fault on nearby pipelines,as well as to determine the safe distance or the maximum parallel length.
Keywords:1 000 kV AC transmission line  single-phase ground fault  oil/gas pipelines  maximum voltage on the pipeline anticorrosive coating  fitting formula  electromagnetic effect  safe distance